| General specifications |
| Signal type | Analog input |
| Functional safety related parameters |
| Safety Integrity Level (SIL) | SIL 2 |
| Supply |
| Connection | terminals 23 , 24- or power feed module/Power Rail |
| Rated voltage | 20 ... 30 V DC |
| Rated current | approx. 100 mA |
| Power dissipation/power consumption | ≤ 2 W / 2.2 W |
| Interface |
| Programming interface | programming socket |
| Input |
| Connection side | field side |
| Connection | terminals 1, 2, 3, 4, 6 |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 |
| | Types of measuring | 2-, 3-, 4-wire technology |
| | Lead resistance | max. 50 Ω |
| | Measurement loop monitoring | sensor breakage, sensor short-circuit |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) |
| | Cold junction compensation | external and internal |
| | Measurement loop monitoring | sensor breakage |
| Potentiometer | 0.8 ... 20 kΩ |
| | Types of measuring | 2-, 3-, 5-wire technology |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV |
| Input resistance | ≥ 250 kΩ (0 ... 10 V)
min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) |
| Measuring current | approx. 400 ?A with resistance measuring sensor |
| Output |
| Connection side | control side |
| Connection | output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8 , 7- |
| Output I, II | relay |
| | Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
| | Mechanical life | 5 x 107 switching cycles |
| | Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Output III | Analog current output |
| | Current range | 0 ... 20 mA or 4 ... 20 mA |
| | Open loop voltage | max. 24 V DC |
| | Load | max. 650 Ω |
| | Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
| Collective error message | Power Rail |
| Transfer characteristics |
| Sampling rate | approx. 700 ms |
| Indicators/settings |
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons
via PACTware |
| Labeling | space for labeling at the front |