| Supply |
| Connection | terminals 11 , 12- terminals 8 , 9- |
| Rated voltage | 20 ... 30 V DC
The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
| Fusing | 5 A
recommended maximum utilization of the fuse: 80 % |
| Power dissipation | ≤ 2.4 W |
| Output |
| Connection | Power Rail |
| Output rated operating current | max. 4 A |
| Fault signal | relay output: NO contact |
| Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Indicators/settings |
| Display elements | LEDs |
| Control elements | DIP-switch |
| Configuration | via DIP switches |
| Labeling | space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility | |
| | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity |
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 ?C (-4 ... 140 ?F) |
| Mechanical specifications |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| Certificate | T?V 00 ATEX 1618 X |
| | Marking |

II 3G Ex nA nC IIC T4 |
| Directive conformity | |
| | Directive 2014/34/EU | EN 60079-0:2012 A11:2013 , EN 60079-15:2010 |
| International approvals |
| FM approval | |
| | Control drawing | 116-0160 |
| IECEx approval | IECEx UL 16.0051X |
| | Approved for | Ex nA nC IIC T4 Gc |