| General specifications |
| Signal type | Analog output |
| Functional safety related parameters |
| Safety Integrity Level (SIL) | SIL 2 |
| Supply |
| Connection | Power Rail or terminals 7 , 8- |
| Rated voltage | 20 ... 35 V DC |
| Ripple | within the supply tolerance |
| Rated current | ≤ 50 mA |
| Power dissipation | 1.2 W |
| Input |
| Connection side | control side |
| Connection | terminals 9 , 10-, 11 |
| Voltage drop | approx. 4 V at 20 mA |
| Limit | Input current: approx. ≤40 mA ; input voltage: ≤ 35 V |
| Transmission range | 0 ... 20 mA |
| Output |
| Connection side | field side |
| Connection | terminals 1 , 2- |
| Current | 0 ... 20 mA |
| Load | max. 850 Ω |
| Voltage | 17 V at 20 mA |
| Transfer characteristics |
| Accuracy | 0.1 % |
| Rise time | < 10 ms |
| Indicators/settings |
| Display elements | LED |
| Labeling | space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility | |
| | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity |
| Insulation coordination | EN 50178 |
| Galvanic isolation | EN 50178 |
| Degree of protection | IEC 60529 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 ?C (-4 ... 140 ?F) |
| Mechanical specifications |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 100 g |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| Certificate | T?V 99 ATEX 1499 X |
| | Marking | 
II 3G Ex nA II T4 |
| Directive conformity | |
| | Directive 2014/34/EU | EN 60079-0:2012 A11:2013 , EN 60079-15:2010 |